The HID VertX sub-panels (also known as interface panels) can be used with
either HID VertX V1000 network controllers or Genetec™ access control appliances (Synergis™ Master
Controller and Synergis™ Cloud
Link).
VertX V100
Characteristics |
Specifications |
Power supply |
9 – 18 VDC |
Average operating current at 12 VDC (0 readers) |
60 mA |
Average operating current at 12 VDC (2 readers) |
600 mA |
Operating temperature range |
32 ° – 122 ° F ( 0 ° – 50 ° C) |
Humidity |
5% to 95% non-condensing |
VertX V200
Characteristics |
Specifications |
Power supply |
9 – 18 VDC |
Average operating current at 12 VDC |
50 mA |
Resistors for input supervision |
1 – 10 kohm |
Operating temperature range |
32 ° – 122 ° F ( 0 ° – 50 ° C) |
Humidity |
5% to 95% non-condensing |
VertX V300
Characteristics |
Specifications |
Power supply |
9 – 18 VDC |
Average operating current at 12 VDC |
60 mA |
Relay rating |
2 A @ 30 VDC (maximum load) |
Operating temperature range |
32 ° – 122 ° F ( 0 ° – 50 ° C) |
Humidity |
5% to 95% non-condensing |
Cable specifications
When attaching the interface modules to their controllers, make sure you do not exceed the
recommended cable lengths.
Cable type |
Maximum length |
Description |
Wiegand |
500 ft. (152 m) to reader |
ALPHA 1299C, 22AWG, 9-conductor, stranded, overall shield. Fewer conductors
needed if all control lines are not used. |
RS-485 |
4000 ft. (1220 m) to controller |
Belden 3105A, 22AWG twisted pair, shielded 100 Ω cable, or equivalent. |
Ethernet |
328 ft. (100 m) |
Cat5, Cat5E and Cat6. |
Hi-O CAN bus |
100 ft. (30 m) |
22AWG gauge. Maximum between drops 30 ft. (10 m). |