This section lists the settings found in Elevator configuration tabs, in the
Area view task.
Elevator - Floors tab
In the
Floors tab, you can configure the physical wiring
relationships between the access control unit and the elevator floors, and select cameras
used to monitor this elevator in
Security
Desk.
Preferred unit:
Access control unit that manages this elevator cab’s panel.
Elevator cab reader:
Reader interface that is used inside the elevator cab.
The available reader settings are:
PIN entry timeout:
This sets the entry timeout for the PIN after the card has been read. For example, at
the default (5 seconds), you have 5 seconds to enter all the PIN digits.
Use card and PIN:
Set to ON to change the reader mode to Card and PIN and use the
Schedule drop-down list to select when this mode applies. When
not in a scheduled time period, the reader behaves in Card only mode.
Camera:
Camera that monitors this elevator in Security
Desk.
Floors:
Push button relays and inputs connected to the elevator floor buttons.
Push button relay:
Output relays assigned to the different elevator floor buttons. Access granted
events cause an output relay to close, which enables the button-push to request
a certain floor.
Floor tracking:
Inputs assigned to elevator floor buttons. When you assign inputs, Security
Center can take note of which floor
button was pushed.
Cameras:
Cameras used to monitor the elevator door on each floor.
Elevator - Access tab
In the
Access tab, you can configure the access rules applied to
each of the elevator floor, and determine when access to the elevator floors is controlled
and when
free access is available.
Access rules:
Select access rules to determine which floor buttons are enabled, when, and for
which cardholders. Different access rules can be applied to different floors, or
applied to all floors.
Exceptions:
Determine if there are any exceptions to the access rule you set.
Schedule:
Select a schedule when the exception applies.
Floor:
Select which floors the exception applies to.
Mode:
Select whether access to the elevator floor is free or
controlled during the exception schedule.
Elevator - Advanced tab
In the
Advanced tab, you can configure the advanced behavior of this elevator.
Grant time:
How long the elevator floor button is enabled after an access granted event is
generated.
Free access when the output relay is:
Normal:
Floor access is granted when the access control unit output relay is
de-energized. This means that a power loss results in free access to the
floor.
Active:
Floor access is granted when the access control unit output relay is
energized. This mean that a power loss results in floor access being
denied.