This section lists the settings found in HID access control unit
Synchronization tab, in the Access control task.
This tab lets you configure the type of synchronization you want between the unit and its Access
Manager.
Last update:
Indicates the date and time of the last successful synchronization with the unit.
Next update:
Date and time of the next scheduled synchronization with the unit.
Configuration expires on:
Depends on whether temporary access rules are used or not.
- If no temporary access rules are used: Indicates the date and time when the unit
can no longer fully function independently of the Access Manager. This is due to the
limited scheduling capability of the HID access control unit. You need to
synchronize before the expiration date to ensure that the unit works properly on its
own.
- If temporary access rules are used: Indicates the date and time the next
synchronization should happen based on the rule activation and expiration date and
time of the temporary access rules.
CAUTION: HID VertX units expire after one year. Past the expiration
date, the unit stops working properly.
Synchronize:
Click this button to send everything that changed since the last synchronization to
the unit. This operation may cause a short service disruption if there are changes to
door unlock schedules.
Synchronize and restart:
Click this button to send the full configuration to the unit and restart the unit.
This operation will cause service disruption.
Synchronization options
You can select how frequently you want the unit synchronization to occur.
Automatically:
This is the recommended setting.
Any configuration change is sent to the access
control unit 15 seconds after the change is saved by the Config
Tool, Web Client or Security Desk. Only
configurations that affect that particular unit are sent.
Daily:
The unit is synchronized daily, at the specified times.
Every:
The unit is synchronized weekly, at the specified day and time.
Manual:
The unit is only synchronized when you click
Synchronize
now.
Make sure you synchronize the unit before the configuration
expires.